Highlights
Part No. 622-333-0-10 Bar VDO Oil Pressure Sender Switch with 1/8 Thread
Fits FG Wilson and Olympian Genset Models with 0-10 Bar Oil Pressure Guages(12 and 24V)
Supersede to obsolete Part No. 622-137.
Specification
Brand:Holdwell
Details
Oil Pressure Sender Switch 622-333 for FG Wilson Generators
Part Number: 622-333, 622333, 622-331, 622-137
Description:
Fit to all FG Wilson and Olympian genset models with 0-10 bar oil pressure gauges (12 and 24V) .
0-5 bar oil pressure sender/switch also available.
Specification:
Terminal G: Is the sender and wire "OP" should be connected to this tterminal - with the wire disconnected,
The terminal should read close to 10 ohms to ground with genset off.
Terminal WK: Is the switch and *wire "15" should be connected to this terminal - with the wire disconnected,
The terminal should read less than 1 ohm to ground with genset off.
* Wire "15" will not be connected on 2300 & 2800 electronic engines, since the engine's Electronic Control
Module will control the low oil pressure shutdown.